| COMPOSITE INSULATORS -132kV |
|
|
| |
| |
|
|
| |
|
|
| |
| Sl.no |
Parameter |
Unit |
110kV |
110kV |
132kV |
132kV |
| 1 |
Shed Diameter |
mm |
142or/132/112 |
142or/132/112 |
142or/132/112 |
142or/132/112 |
| 2 |
Unit Spacing |
mm |
1460 |
1460 |
1450 |
1460 |
| 3 |
Creepage Distance |
mm |
3870 |
3870 |
4300 |
4300 |
| 4 |
Arcover Distance |
mm |
1175 |
1175 |
1210 |
1210 |
| 5 |
Electro-Mechanical Min. Failing Load |
kN |
70/90 |
120 |
70/90 |
120 |
| 6 |
Coupling Designation |
mm |
16 |
20 |
16 |
20 |
| 7 |
Pf-Wet Withstand Voltage |
kV |
185 |
185 |
275 |
290 |
| 8 |
Pf-Dry Withstand Voltage |
kV |
200 |
200 |
325 |
335 |
| 9 |
DRY-Lightning Impulse Withstand Voltage |
kVp |
450 |
450 |
650 |
650 |
| 10 |
Visible Discharge Test Voltage |
kV |
88 |
88 |
105 |
105 |
| 11 |
Weight of Unit (Approx) |
kg |
6.0 |
6.8 |
7.5 |
8.0 |
|
|
| |
|
|
| |
| |
1. Specific creepage distance from 16 mm / kV to 40 mm / kV
2. Length ranges from 285 mm to 4080 mm
3. Specified mechanical loads from |
| |
| |
a. 45 KN to 120 KN for 33 KV to 132 KV.
b. 70 KN to 160 KN for 220 KV.
c. 120 KN to 160 KN for 400 KV. |
|
| |
4. For specific requirement, contact: CBU / Marketing, Malleshwaram, Bangalore....560012 |
|
|
|
| |
|
|
|
|
|
 |
|
|
|
 |
|
|