| SOLID CORE POST INSULATOR TYPE 132kV |
|
|
|
|
| |
| |
|
|
| |
|
|
| |
| SL. No. |
PARAMETERS |
Unit |
|
| 1 |
TYPE
|
|
SOLID CORE |
| 2 |
VOLTAGE CLASS
|
kV |
132 |
| 3 |
HEIGHT OF INSULATOR
|
|
1500 ± 2.5 |
| 4 |
TOTAL CREEPAGE DISTANCE
|
mm |
3625 |
| 5
|
WITHSTAND TEST VOLTAGE
|
|
|
DRY
|
kV |
275 |
WET
|
kV |
275 |
IMPULSE
|
kvp |
650 |
| 6
|
MECHANICAL STRENGTH
|
|
|
CANTILEVER STRENGTH
|
kN |
8 |
TENSILE STRENGTH
|
kN |
95 |
TORSION STRENGTH
|
kN |
4 |
COMPRESSION STRENGTH
|
kN |
190 |
| 7
|
PITCH CIRCLE DIAMETER
|
|
|
TOP
|
mm |
127 |
BOTTOM
|
mm |
225 |
| 8 |
SPECIFICATION |
|
IS: 2544/ IS: 5350/ IEC: 60273 |
|
|
| |
Manufacturing Capabilities |
|
| |
|
| |
|
| |
| |
| |
1. Specific creepage distance from 16 mm /kV to 40 mm / kV
2. Height ranges from 254 mm to 3650 mm
3. Cantilever/Bending strengths from |
| |
| |
a) 2 kN to 16 kN for 33 kV to 132 kV.
b) 2 kN to 10 kN for 220 kV.
c) 2 kN to 8 kN for 400 kV. |
|
| |
4. Top PCD varying from 50 mm to 127 mm.
5. Bottom PCD varying from 50 mm to 300 mm.
6. For specific requirement, contact: CBU / Marketing, Malleshwaram, Bangalore....560012 |
|
|
|
|
|
| |
|
|
|
|
|
 |
|
|
 |
|
|